한국해양대학교

Detailed Information

Metadata Downloads

전력용 피뢰기의 열화진단 전문가시스템 개발에 관한 연구

DC Field Value Language
dc.contributor.author 金明珍 -
dc.date.accessioned 2017-02-22T06:57:21Z -
dc.date.available 2017-02-22T06:57:21Z -
dc.date.issued 2002 -
dc.date.submitted 56797-10-27 -
dc.identifier.uri http://kmou.dcollection.net/jsp/common/DcLoOrgPer.jsp?sItemId=000002174010 ko_KR
dc.identifier.uri http://repository.kmou.ac.kr/handle/2014.oak/10073 -
dc.description.abstract This thesis deals with an effect of a single and a quadruple lightning impulse currents on electrical characteristics of ZnO blocks, and an expert system to diagnose deterioration of arresters. Lightning arresters are the best protective device on electric power systems to transient overvoltages caused by lightning discharge and switching operation. Though there have been accomplished technical and economical renovations by the development of a ZnO block having excellent nonlinear I-V resistive characteristics, substantial parts of the power system failures are still occupied by deterioration of lightning arresters. Electrical characteristics of ZnO blocks are deteriorated by repeated impulse current, and the deteriorated ZnO block is brought to a thermal runaway and finally destroyed. It is therefore important to estimate the change of electrical characteristics of ZnO blocks. In this study, an accelerated deterioration test is carried out to deduce the parameters needed for diagnosing arrester deterioration, and leakage current components are measured. Also, wave height distribution of the leakage current with the progress of arrester deterioration is analyzed. From the experimental results, the wave height distribution of the leakage current showed a conspicuous difference even in an immaterial leakage current increase. The use of wave height distribution of the leakage current in deterioration diagnostic technique makes more accurate diagnosis than the conventional method using only a leakage current value. Finally, the expert system based on the experimental results is developed, and the effectiveness of the system is estimated in a 18[kV] lightning arrester, a 72[kV] and a 170[kV] gas insulated switchgear system. -
dc.description.tableofcontents 목차 목차 = i 그림 및 표목차 = ii Abstract = iv 제 1 장 서론 = 1 제 2 장 이론 = 5 2.1 피뢰기의 구조 및 특성 = 5 2.2 열화진전기구 = 12 2.3 열화진단기술 = 14 제 3 장 뇌충격전류에 의한 가속열화시험 = 23 3.1 실험장치 및 방법 = 23 3.2 동작개시전압 및 누설전류의 변화 = 30 3.3 열화진전에 따른 누설전류의 파고분포 = 34 제 4 장 열화진단 전문가 시스템 및 적용 평가 = 36 4.1 열화진단 전문가 시스템 = 36 4.2 적용 실험 = 44 제 5 장 결론 = 54 참고문헌 = 56 -
dc.publisher 한국해양대학교 -
dc.title 전력용 피뢰기의 열화진단 전문가시스템 개발에 관한 연구 -
dc.title.alternative A Study on the Development of an Expert System to Diagnose Lightning Arrester Deterioration -
dc.type Thesis -
Appears in Collections:
전기공학과 > Thesis
Files in This Item:
000002174010.pdf Download

Items in Repository are protected by copyright, with all rights reserved, unless otherwise indicated.

Browse