TEV 검출에 의한 수배전반의 절연진단에 관한 연구

DC Field Value Language
dc.contributor.advisor 길경석 -
dc.contributor.author 김우현 -
dc.date.accessioned 2020-07-20T11:44:20Z -
dc.date.available 2020-07-20T11:44:20Z -
dc.date.issued 2019 -
dc.identifier.uri http://repository.kmou.ac.kr/handle/2014.oak/12257 -
dc.identifier.uri http://kmou.dcollection.net/common/orgView/200000216819 -
dc.description.abstract Switchboard is a major power facility that is equipped for electricity distribution, switching, metering, and diagnosis. The modern society is highly relies on electrical energy and power outage may cause great economic and technical losses. As a result, it is necessary to diagnosis the condition of switchboard to ensure its reliable operation. During the operation of power apparatus such as transformers and circuit breakers, partial discharge(PD) may occur due to electric field concentration or insulation deterioration. Accompanying with PD, the transient earth voltage(TEV) will propagate along the metal or ground surface of switchboard. In this paper, for the purpose of insulation diagnosis of switchboard and related power apparatus, a TEV sensor was designed and fabricated for on-line PD detection. The insulation defects that cause insulation breakdown in switchboard were classified into protrusion on conductor, protrusion on enclosure, and free particle. The simulated TEV experiments were carried out and the characteristics of TEV sensor were analyzed. The fabricated TEV sensor could detect the signal with a frequency range from 1MHz to 100MHz and sample PD signals with a response time less than 8ns. In addition, the detection sensitivity depending on apparent charge and sensor type were studied. It was verified that the sensor with a diameter of 70mm and a thickness of 1mm was optimal for detect PD with a magnitude of 10pC∼100pC. The sensor used for application and evaluation had a sensitivity of 1.2 mV/pC. The electrical detection method specified in KS C IEC 60270 is a reference of PD signal acquisition, however, it can not be used for on-line detection of switchboard. The TEV sensor is a non-electrical method that can obtain same discharge patterns as the electrical method and overcome the limitations of existing method. The TEV sensor proposed in this paper had the optimal detection sensitivity and economic advantage, which can be used for condition monitoring and asset management of switchboards. -
dc.description.tableofcontents 목 차 i 그림 및 표 목차 ii Abstract iv 제 1 장 서 론 1 제 2 장 이 론 3 2.1 수배전반 3 2.2 절연열화와 부분방전 6 2.3 TEV의 발생원리 19 제 3 장 TEV 센서 23 3.1 설계 및 제작 23 3.2 센서의 특성 평가 31 제 4 장 적용 평가 40 4.1 실험계 40 4.2 TEV의 주파수 스펙트럼 43 4.3 결함별 PRPD 패턴 47 4.4 TEV의 거리 의존성 51 제 5 장 결 론 52 참 고 문 헌 54 -
dc.format.extent 69 -
dc.language kor -
dc.publisher 한국해양대학교 대학원 -
dc.rights 한국해양대학교 논문은 저작권에 의해 보호받습니다. -
dc.title TEV 검출에 의한 수배전반의 절연진단에 관한 연구 -
dc.type Dissertation -
dc.date.awarded 2019-08 -
dc.contributor.alternativeName Kim Woo Hyun -
dc.contributor.department 대학원 전기전자공학과 -
dc.contributor.affiliation 한국해양대학교 대학원 전기전자공학과 -
dc.description.degree Master -
dc.identifier.bibliographicCitation 김우현. (2019). TEV 검출에 의한 수배전반의 절연진단에 관한 연구. , (), -. -
dc.subject.keyword TEV, 부분방전, 절연진단, 수배전반 -
dc.title.translated A Study on the Insulation Diagnosis of Switchboard by Detection of TEV Signals -
dc.contributor.specialty 고전압응용기술 -
dc.identifier.holdings 000000001979▲200000001277▲200000216819▲ -