한국해양대학교

Detailed Information

Metadata Downloads

몰드변압기 절연진단을 위한 부분방전 측정 및 분석

DC Field Value Language
dc.contributor.author 정광석 -
dc.date.accessioned 2017-02-22T06:03:51Z -
dc.date.available 2017-02-22T06:03:51Z -
dc.date.issued 2011 -
dc.date.submitted 56959-08-17 -
dc.identifier.uri http://kmou.dcollection.net/jsp/common/DcLoOrgPer.jsp?sItemId=000002174906 ko_KR
dc.identifier.uri http://repository.kmou.ac.kr/handle/2014.oak/9033 -
dc.description.abstract This thesis deals with the measurement and analysis of partial discharge(PD) for insulation diagnosis of cast-resin transformers. A PD measurement system which consists of a capacitive probe, a coupling network and an amplifier is set up to detect PD pulse. The capacitive probe is proposed to detect PD pulses without connecting a high voltage conductor. The coupling network is designed to attenuate 60[Hz] by 130[dB], and its low cutoff frequency of -3[dB] is 100[kHz]. The amplifier with the gain of 40[dB] is fabricated, and its frequency bandwidth is in ranges of 500[Hz]∼45[MHz]. Sensitivity of the PD measurement system is 0.35[㎷/pC] for positive and 0.45[㎷/pC] for negative polarity, respectively. A planar-planar and a planar-point(10[㎛]) electrode are fabricated to simulate insulation defects in cast-resin transformers. In the experiment, the rise-time of PD pulses is about 11[㎱] in the defects, and the phase distribution of PD pulses is in ranges of 8[°]∼90[°] and 192[°]∼277[°] in the planar-planar electrode, and of 345[°]∼128[°] and 165[°]∼295[°] in the planar-point(10[㎛]) electrode. The results showed that the proposed PD measurement system can detect PD pulses and analyze their electrical characteristics such as the magnitude and the phase distribution of PD pulses. -
dc.description.tableofcontents 목 차 목 차 ⅰ 그림 목차 ⅱ Abstract ⅲ 제 1 장 서 론 1 1.1 연구배경 및 필요성 1 1.2 연구목적 3 1.3 연구내용 및 활용방안 4 제 2 장 이 론 5 2.1 부분방전의 발생 5 2.2 부분방전의 검출원리 10 제 3 장 실험 및 방법 22 3.1 측정장치 23 3.2 실험방법 32 제 4 장 결과 및 분석 37 4.1 교정실험 37 4.2 위상분포와 파형 40 제 5 장 결 론 46 참 고 문 헌 47 -
dc.language kor -
dc.publisher 한국해양대학교 대학원 -
dc.title 몰드변압기 절연진단을 위한 부분방전 측정 및 분석 -
dc.title.alternative Partial Discharge Measurement and Analysis for Insulation Diagnosis of Cast-resin Transformers -
dc.type Thesis -
dc.date.awarded 2011-02 -
dc.contributor.alternativeName Kwang-Seok Jung -
Appears in Collections:
전기전자공학과 > Thesis
Files in This Item:
000002174906.pdf Download

Items in Repository are protected by copyright, with all rights reserved, unless otherwise indicated.

Browse