한국해양대학교

Detailed Information

Metadata Downloads

봉상접지극의 과도임피던스 특성

DC Field Value Language
dc.contributor.author 金一權 -
dc.date.accessioned 2017-02-22T06:08:02Z -
dc.date.available 2017-02-22T06:08:02Z -
dc.date.issued 2001 -
dc.date.submitted 56797-10-27 -
dc.identifier.uri http://kmou.dcollection.net/jsp/common/DcLoOrgPer.jsp?sItemId=000002173866 ko_KR
dc.identifier.uri http://repository.kmou.ac.kr/handle/2014.oak/9140 -
dc.description.abstract This thesis deals with the correlation of the transient impedance and its parameters with the stationary resistance of grounding systems to a square pulse current and a lightning impulse current. In experiment, the grounding system consists of a single grounding rod(φ10[mm], 1[m]) and/or a triple-grounding rods of equilateral triangles with 5[m] spacing for operation. To analyze the transient impedance characteristics of the grounding system, a pulse generator which can produce square wave of a 30[ns] rise-time and a 20[㎲] pulse duration is designed and fabricated. Also, impulse current tests using the standard 8/20[㎲] wave specified in IEC 61000-4-5 were carried out on the grounding system to simulate the transient characteristics in an actual field condition such as a grounding system for power distribution lines. The injected current in the grounding system and the developed potential were recorded, and the time variation of the transient impedance were calculated as the ratio of the potential rising to the injected current at each time. The experimental results showed that the transient impedance reaches its maximum value very fast (around 250[ns]) and consecutively is returned to the value of the stationary impedance. The transient impedance and the effective surge impedance Z3 which defines economic protection level were quite higher than the stationary resistance. The grounding impedance is decreased by the application of the triple-rods grounding system, and its effect is decreased as the frequency of the current is increased due to the inductance of the grounding leads. It is therefore important to minimize the inductance of the grounding rods and leads to obtain the lowest grounding impedance and the lowest potential rising in a grounding system. -
dc.description.tableofcontents 그림 및 표 목차 = ⅲ Abstract = Ⅴ 제 1 장 서론 = 1 1.1 연구 배경 및 필요성 = 1 1.2 연구 목적 및 내용 = 2 제 2 장 이론 = 4 2.1 접지저항 = 4 2.1.1 대지저항률 = 6 2.1.2 접지저항 측정 = 10 2.2 접지임피던스 = 12 2.2.1 봉상접지극 = 13 2.2.2 임피던스 파라미터 = 20 제 3 장 실험장치 및 방법 = 22 3.1 실험장치 = 22 3.1.1 직각파 전류 발생장치 = 22 3.1.2 뇌충격 전류 발생장치 = 28 3.2 측정계의 구성 및 실험방법 = 30 제 4 장 실험결과 및 고찰 = 35 4.1 직각파 전류에 대한 과도접지임피던스 = 36 4.2 뇌충격 전류에 대한 과도접지임피던스 = 41 제 5 장 결론 = 47 참고문헌 = 49 -
dc.publisher 한국해양대학교 대학원 -
dc.title 봉상접지극의 과도임피던스 특성 -
dc.title.alternative Transient Impedance Characteristics of Grounding Rods -
dc.type Thesis -
Appears in Collections:
전기공학과 > Thesis
Files in This Item:
000002173866.pdf Download

Items in Repository are protected by copyright, with all rights reserved, unless otherwise indicated.