한국해양대학교

Detailed Information

Metadata Downloads

유입식 변압기의 부분방전 진단에 관한 연구

DC Field Value Language
dc.contributor.author 이정윤 -
dc.date.accessioned 2017-02-22T06:50:28Z -
dc.date.available 2017-02-22T06:50:28Z -
dc.date.issued 2012 -
dc.date.submitted 57014-05-25 -
dc.identifier.uri http://kmou.dcollection.net/jsp/common/DcLoOrgPer.jsp?sItemId=000002175640 ko_KR
dc.identifier.uri http://repository.kmou.ac.kr/handle/2014.oak/9894 -
dc.description.abstract This thesis deals with the radiated electromagnetic wave detection of partial discharge(PD) in oil for insulation diagnostics of oil-immersed transformers. Partial discharge by insulation deterioration of power facilities can lead to failure if not detected earlier. So far, the two main insulation diagnostic techniques of the oil-immersed transformer were the dissolved gas analysis(DGA) method in insulation oil and the acoustic method. These two methods, however, accompany some problems in installment and sensitivity. Therefore, research on the detection methods of radiated electromagnetic waves caused by partial discharges in insulation oil is now being actively conducted. From these backgrounds this thesis suggests the optimal detection method, analyzing frequency spectrum of radiated electromagnetic wave by partial discharge(PD) in oil. Electrode systems were fabricated to simulate the defects that might occur in oil-immersed transformers. Frequency spectrum of radiated electromagnetic wave in oil was analyzed by broad-band bi-conical antennas(300MHz~2GHz) and a spectrum analyzer(9kHz~3GHz). Frequency components for most defects showed high distribution at 500MHz. From the result, a narrow-band monopole antenna with the center frequency at 500MHz was made. The length of the antenna was 150mm. The propagation characteristic of the monopole antenna was evaluated by the network analyzer(40MHz~40GHz). It was suitable to detect the signal of partial discharge in oil. The measurement system which consists of the prototype monopole antenna, LNA(Low Noise Amplifier), oscilloscope and spectrum analyzer was evaluated from the partial discharge in insulation oil. It could detect all defects used in the experiment. -
dc.description.tableofcontents 목 차 ⅰ 그림 목차 ⅲ Abstract ⅴ 제 1 장 서 론 1 1.1 연구배경 1 1.2 연구목적 및 내용 3 제 2 장 이 론 4 2.1 절연열화와 부분방전 4 2.1.1 절연열화 4 2.1.2 부분방전 5 2.2 절연진단기술 10 2.2.1 유중 가스 분석법 11 2.2.2 부분방전 검출법 13 제 3 장 설계 및 제작 19 3.1 결함전극계 19 3.2 모노폴 안테나 22 제 4 장 실험 및 분석 31 제 5 장 결 론 39 참 고 문 헌 41 -
dc.language kor -
dc.publisher 길경석 -
dc.title 유입식 변압기의 부분방전 진단에 관한 연구 -
dc.type Thesis -
dc.date.awarded 2013-02 -
Appears in Collections:
전기전자공학과 > Thesis
Files in This Item:
000002175640.pdf Download

Items in Repository are protected by copyright, with all rights reserved, unless otherwise indicated.

Browse